LRTP Reducer Kit

Ordering Information

The Hubbell Power Systems 600 A 15 or 25kV rated LRTP Deadbreak Termination System is designed to connect medium voltage UD cable to switchgear, transformers, sectionalizing cabinets and UD vault applications. It is fully compliant with IEEE-386 Standard and mates with bushing components that also comply with the IEEE-386 Standard. The LRTP system uses a threaded compression lug allowing the LRTP to be threaded into the T-body forming an integral termination system. The T-body can be ordered with or without a capacitive test point.

The LRTP system is ideal for applications where the termination will be moved to achieve a visible break and ground. The integral termination system, T-body and LRTP as one unit, makes it easier to install and remove from the mating bushing interface.

The 200-amp loadbreak interface can be either 15kV or 25kV rated. This interface allows for live test, phasing and visible ground. In addition, it can be used to add a tap, or install an Arrester Elbow to protect your UD system from voltage surges.

600 Amp Deadbreak 25kV Class Ratings
Description Ratings
Operating Voltage
Maximum line-to-ground
15.2kV
BIL
Impulse withstand 1.2 x 50 μsec
125kV
Withstand Voltage
AC One Minute
DC Fifteen Minute
40kV
78kV
Corona Extinction Level @
3pC Sensitivity
19kV
Continuous Current 600 amp
24 Hour Overload 1,000 A rms
Symmetrical Momentary
Current
25 kA rms sym. for 0.17 sec
10 kA rms sym. for 3.0 sec
200 Amp Rating on LRTP
Description 15kV Class Ratings 25kV Class Ratings
Operating Voltage
Maximum line-to-ground
8.3kV Phase-to-Ground
14.4 Phase-to-Phase
15.2kV Phase-to-Ground
26.3kV Phase-to-Phase
BIL
Impulse withstand 1.2 x 50 μsec
95kV 125kV
Withstand Voltage
AC One Minute
DC Fifteen Minute
34kV
53kV
40kV
78kV
Corona Extinction Level @
3pC Sensitivity
11kV 19kV
Continuous Current 200 amp 200 amp
Switching 10 Operations at 200 A rms at 14.4kV 10 Operations at 200 A rms at 26.3kV
Fault Closure 10 kA rms sym. at 14.4kV for 0.17 sec
after 10 switching operations
10 kA rms sym. at 26.3kV for 0.17 sec
after 10 switching operations
Short Time 10 kA rms sym. for 0.17 sec
3,500 A rms sym. for 3.0 sec
10 kA rms sym. for 0.17 sec
3,500 A rms sym. for 3.0 sec
-top of page-

Ordering Information

Deadbreak LRTP Component Items:

Description Catalog Number
Tee-Body with Test Point 625TBT
Tee-Body without Test Point with Aluminum Stud 625TB
15kV Loadbreak Reducing Tap Plug (LRTP) 615LRTP
25kV Loadbreak Reducing Tap Plug (LRTP) 625LRTP
Cable Adapter 625CAW
Aluminum Compression Connector 625LUGXXT

EXAMPLE: The part number for a 25kV LRTP Kit with Test Point Elbow and an Insulated Cap for 500 Stranded, 260 MIL Cable with an Insulation Diameter of 1.415" is: 625LRTPM33TC.

The kit components include:

  • T-body (test point optional)
  • Cable adapter
  • Threaded Compression lug
  • LRTP (15kV or 25kV)
  • 200 A insulated cap (optional)
  • Installation instructions
  • Lubrication