For sales and support visit:
hubbellpowersystems.com/contact/
Characteristics
Mechanical | Electrical

Suspension (VLS)

0.625" (16mm) Diameter Rod Deadend Insulators

Mechanical Characteristics

Catalog
Numbers
No.
of
Sheds
"X"
Length
inches
(mm)
"D"
Diameter
Inches
(mm)
Net Wt.
pounds
(kg)
Standard Package Qty. 1SML
pounds
(kN)
2RTL
pounds
(kN)
3Proof
pounds
(kN)
Carton Pallet
4050021301 4 11.5
(292)
5.9
(150)
4
(1.8)
12 96 15,000
(70)
7,500
(35)
10,000
(44.5)
4050029001** 4 12.5
(318)
5.9
(150)
4
(1.8)
12 96 15,000
(70)
7,500
(35)
10,000
(44.5)
4050031301 6 17.25
(438)
5.9
(150)
4
(1.8)
12 96 15,000
(70)
7,500
(35)
10,000
(44.5)
4050041301 8 23
(584)
5.9
(150)
5
(2.3)
12 96 15,000
(70)
7,500
(35)
10,000
(44.5)
4050051301 10 28.75
(730)
5.9
(150)
6
(2.8)
12 48 15,000
(70)
7,500
(35)
10,000
(44.5)
4050061301 12 34.5
(876)
5.9
(150)
7
(3.2)
12 48 15,000
(70)
7,500
(35)
10,000
(44.5)
-top of page-

Electrical Characteristics

Catalog
Numbers
Type Leakage
Distance
Inches
(mm)
Dry Arc
Distance
Inches
(mm)
Flashover
ANSI
Critical
Flashover
ANSI
RIV Power Arc
kA cycles
Equivalent
number of
10" x 5-3/4"
Bells
Volt*
Class
Dry-kV Wet-kV Pos-kV Neg-kV Test kV Max. μV
4050021301 VLS-2 23
(584)
11.75
(298)
135 110 225 255 21 <10 150 2 15/25
4050029001** VLS-2 23
(584)
11.75
(298)
135 110 225 255 21 <10 150 2** 15/25
4050031301 VLS-3 39
(991)
18
(457)
190 140 320 330 32 <10 150 3 35/46
4050041301 VLS-4 54
(1372)
23.7
(602)
255 190 420 435 48 <10 150 4 46/69
4050051301 VLS-5 69
(1753)
29.5
(749)
315 245 500 510 48 <10 150 5 69
4050061301 VLS-6 84
(2134)
35.2
(894)
370 305 610 580 48 <10 150 6 69
Suffix Code Tower-end Line-end
1301 ANSI 52-3 Socket ANSI 52-3 Ball
1400 ANSI 52-6 Clevis ANSI 52-6 Tongue
2A07 IEC 16 mm Socket IEC 16 mm Ball

VLS insulators are available with ANSI and IEC ball / socket end fittings and also with clevis/tongue end fittings. Please use the following 4-digit suffix codes after the 6-digit catalog number.

-top of page-
Hubbell Power Systems All contents Copyright© 2001 - Hubbell Incorporated. All rights reserved. Because Hubbell has a policy of continuous product improvement, we reserve the right to change design specifications without notice.
Terms of Use | Contact Us | Site Map | Careers
Insulators